MORE AIR.
THE SAME CINEMA FOCUS.
Balanced ventilation for larger home cinemas, studios and screening rooms. Up to 350 m³/h of air exchange, heat recovery and multi-stage filtration — designed to be planned into the room, not added as an afterthought.

Seal the cinema.
Not the people inside it.
A well-isolated room still needs a deliberate route for fresh air. Opening a door or adding a simple unattenuated vent can undermine the soundproofing around it.
During a long film, the audience adds heat, humidity and carbon dioxide to the room. Larger rooms and more seating increase the importance of planning air exchange alongside the screen, sound system and seating layout.
CineVent 350 provides controlled supply and extract ventilation. The unit, ductwork, silencers and wall or ceiling penetrations are designed as one installation, so the ventilation route can be integrated into the cinema rather than becoming an uncontrolled sound path.
Used air out.
Filtered air back in.
Supply and extract air travel through separate paths. The heat exchanger transfers thermal energy from the outgoing air to the incoming stream without deliberately mixing the two airflows.

Remove used air
Extract air from the occupied room through a planned, acoustically treated duct route.
Retain useful heat
The exchanger recovers a stated 79–81% of heat, depending on fan setting and test conditions.
Prepare the supply air
Multi-stage filtration reduces particles and helps control odours in the incoming air.
Bring fresh air in
Deliver filtered outdoor air back to the room through the separate supply connection.
Exchange the air.
Keep more of the heat.
Simply exhausting warm room air also throws away energy already used to heat it. CineVent transfers part of that energy to the incoming air, reducing the ventilation heat loss compared with a system without heat recovery.
The stated temperature efficiencies are approximately 80%, 81% and 79% at low, medium and high speed. These are manufacturer reference values, not a guarantee of the same recovery under every outdoor condition or duct arrangement.
Ventilation is not
air conditioning.
Fresh-air exchange and active temperature control solve different problems. A demanding cinema may need both.
Exchange the air.
Extracts used air and supplies filtered outdoor air. Air exchange helps remove occupant-generated carbon dioxide and moisture; the heat exchanger limits avoidable heat loss.
Control the temperature.
Provides active heating or cooling. A recirculating room system does not by itself replace the need for outdoor-air ventilation, particularly when several viewers occupy a sealed cinema.
Projectors, amplifiers and people can create significant internal heat gains. Include that load in the cooling review separately from fresh-air sizing.
Choose the airflow.
Plan the quiet operation.
The 350 model has nominal fan settings of 150, 200 and 350 m³/h. Match the setting to occupancy, installed duct resistance and the acoustic target.
80 W · 35 dB
120 Pa stated external pressure
120 W · 40 dB
190 Pa stated external pressure
160 W · 43 dB
225 Pa stated external pressure
Manufacturer figures. Sound levels are not measurements at the cinema seats. Duct losses, mounting, silencers and the surrounding structure affect the installed result. The source gives a sound-measurement tolerance of +5/−7 dB.
Count the audience.
Not just the square metres.
Use the planned number of viewers as an early capacity check, then review the complete ventilation design with your installer.
These examples use a planning reference of 26 m³/h per person. For comparison, an area reference of 1.2 m³/h per m² gives 57.6 m³/h for a 48 m² room. The person and area references are not automatically added together.
An eight-seat cinema therefore gives an occupancy reference of 208 m³/h — already above the 350 model’s medium nominal setting. That makes fan setting, pressure loss and acoustic attenuation part of the design discussion, rather than just selecting a unit by its maximum number.
Planning examples only. Local requirements, room use, target air quality and installed airflow must be checked for the project.
Plan the room and ventilationDo more than exchange air.
Filter the supply.
CineVent combines several filter stages rather than relying on a single coarse filter. Access for regular inspection and replacement is part of a good installation.

Coarse filter
Captures larger dust particles before they reach the finer stages.
Electrostatic stage
An additional washable particle-collection stage in the filter system.
Activated carbon
Helps reduce odours and certain gaseous contaminants.
H13 HEPA
High-efficiency fine-particle filtration for the incoming supply air.
See the room conditions.
Control the ventilation.
The wired panel provides fan-speed, operating-mode, timer, filter-alert and Wi-Fi settings. Tuya app support adds control from a phone.

The listed sensor readings help you follow changes in the room. They should not be confused with a direct measurement of occupancy-generated carbon dioxide.
CineVent 350 does not have built-in CO₂ measurement. Use a separate CO₂ monitor where that reading is needed for occupancy-based operation or indoor-air-quality checks.
More capacity.
A low-profile installation.
The 350 model has its own enclosure and duct sizes. Allow for those dimensions and for maintenance access, not only the visible space occupied by the unit.

Approximate external dimensions
Stated spigot measurement approximately 146 mm
Provide a suitable support and fixing design
Plan the specified horizontal mounting arrangement in a suitable ceiling, wall or technical zone. Filters and serviceable components must remain accessible after the cinema is finished.
The connection and electrical arrangement should follow the current model-specific installation documentation. Do not use the smaller CineVent 150 enclosure drawing as a mounting template for the 350.
The air path is part
of the acoustic design.
A ventilation unit alone does not determine how much sound escapes from a sealed room. The complete duct path must work with the soundproofing construction.
Route and attenuate.
Avoid a short, direct sound path through the wall or ceiling. Select suitable silencers and duct routes without creating excessive resistance or air velocity.
Seal the penetrations.
Detail penetrations, supports and joints so they do not bypass the intended decoupling or leave uncontrolled air leaks through the soundproofing assembly.
Manage condensation.
Specify insulation and vapour control for the actual temperatures and installation zones. Keep supply and extract paths correctly identified and connected.
Keep it maintainable.
Provide access to filters, the controller connection and the unit. A hidden installation still needs a practical service route.
Build maintenance
into the plan.
Inspect the filters regularly and respond to the filter alert. Cleaning and replacement frequency depend on operating hours and outdoor air quality, not only the calendar.
The product guidance gives a typical HEPA and carbon-filter replacement interval of one to two times per year. Follow the current filter instructions: a washable coarse or electrostatic stage does not mean that every element in the filter pack can be washed.
CineVent 350.
The model-specific specification.
| Product type | Balanced supply and extract ventilation with heat recovery |
|---|---|
| Mounting | Specified horizontal arrangement in a suitable wall, ceiling or technical zone |
| Nominal airflow · low / medium / high | 150 / 200 / 350 m³/h |
| Power consumption · low / medium / high | 80 / 120 / 160 W |
| Stated sound level · low / medium / high | 35 / 40 / 43 dB |
| Stated external pressure · low / medium / high | 120 / 190 / 225 Pa |
| Temperature efficiency · low / medium / high | Approx. 80 / 81 / 79% |
| Duct connections | 4 × Ø150 mm · stated spigot size approx. 146 mm |
| Approximate dimensions | 853 × 752 × 217 mm |
| Weight | Approx. 27 kg |
| Power supply | 220 V ~ 50 Hz |
| Filtration | Coarse, electrostatic, activated carbon and H13 HEPA filter functions |
| Control | Wired controller and Tuya app over Wi-Fi |
| Listed sensor readings | Temperature, humidity, PM2.5, PM10 and VOC |
| Built-in CO₂ sensor | No |
| DreamScreen MSRP | EUR 2,499 · excluding VAT / taxes, freight and installation |
Manufacturer reference values, including a stated +5/−7 dB sound-measurement tolerance. Confirm the current installation specification and model revision before fixing dimensions or designing the duct system.
Plan the complete installation.
Use the current 350-model data for enclosure dimensions, electrical connection and ductwork. DreamScreen can help your project partner confirm the required documents.
Download manual — English (PDF, 2026-10-23)
Your local DreamScreen partner confirms availability, delivery, installation and final local pricing.
